KYN28A-12 is the switchgear apply in the single busbar power system and single busbar sectionalized power system with three-phase AC 50Hz,7.2~12kV.It can be used for receiving & distributing electric power of the transmission and distribution control.
2. Working Condition
Indoor ambient temperature:
Max. temperature: +40℃
Daily average temperature: +35℃
Min. temperature: -15℃
Indoor ambient humidity:
Daily average relative humidity: ≤95%
Monthly average relative humidity: ≤90%
Altitude for place of installation : ≤1000m
Earthquake intensity: ≤magnitude 8
Applicable in the places without fire, explosive risk, serious polluted and chemical corrosive.
(Exceeding above working condition is available as customized product)
| 
			 Rated voltage  | 
			
			 kV  | 
			
			 12  | 
		|
| 
			 Rated insulated level  | 
			
			 1min Power frequency withstand voltage (available value)  | 
			
			 kV  | 
			
			 42  | 
		
| 
			 Lighting impulse withstand voltage(peak value)  | 
			
			 kV  | 
			
			 75  | 
		|
| 
			 Rated frequency  | 
			
			 Hz  | 
			
			 50  | 
		|
| 
			 Rated current of main busbar  | 
			
			 A  | 
			
			 630,1250,1600,2000,2500,3150,4000﹡  | 
		|
| 
			 Rated current of branch busbar  | 
			
			 A  | 
			
			 630,1250,1600,2000,2500,3150,4000  | 
		|
| 
			 4s Thermal stability current (available value)  | 
			
			 kA  | 
			
			 16,20,25,31.5,40﹡﹡  | 
		|
| 
			 Rated dynamic stability current(peak value) ﹡﹡﹡  | 
			
			 kA  | 
			
			 40,50,63,80,100  | 
		|
Remark:
﹡----it needs to be equipped with ventilation device.
﹡﹡----At the rate of 40kA is 3 seconds.
﹡﹡﹡----The short-circuit capacity of instrument transformer needs to be considered separately.
4. Standard
----IEC62271-200:2003
----GB3906-2006
----GB/T11022-1999
----DL/T 404-2007